Carrier Personal Lift ZONECC3Z User Manual

ZONECC3Z(AC/HP)01  
Installation and Start-Up Instructions  
TABLE OF CONTENTS  
This instruction covers the physical installation and start up of the  
Carrier 3-Zone system. Use this instruction to guide the actual  
installation process after all the air side decisions have been made.  
Page  
SAFETY CONSIDERATIONS...................................................1  
INSTALLATION CONSIDERATIONS....................................1  
INTRODUCTION ........................................................................1  
INSTALLATION ......................................................................1-4  
• Check Equipment And Job Site ..............................................1-2  
• Component Location And Wiring Considerations.....................2  
• Install Components......................................................................2  
• Install Zone Dampers...............................................................2-4  
• Install Barometric Bypass Damper.............................................4  
• Install Leaving Air Temperature (LAT) Sensor.........................4  
• Install Heat Pump Temperature (HPT) Sensor ..........................4  
SYSTEM WIRING...................................................................4-5  
• Wire Thermostats ........................................................................4  
• Wire Equipment...........................................................................4  
• Wire Dampers..............................................................................5  
• Wire Remainder...........................................................................5  
UNDERSTANDING SYSTEM OPERATION ......................6-7  
SYSTEM SETUP ....................................................................7-10  
NOTE: Read the entire instruction manual before starting the  
installation.  
1. Install in non-condensing areas with ambients between 32°F  
and 158°F.  
2. A TXV is required on the indoor coil when used with all  
residential split system equipment.  
3. A separate transformer is not needed to power the 3-Zone  
system. Up to five dampers may be used in each zone by  
electrically connecting them in parallel.  
4. Load calculations must be performed for each zone’s peak  
demand. Size each zone duct for at least its peak demand plus  
25%. Size equipment for the building block load, not the sum  
of zone peak demands. It is important that the equipment not  
be oversized.  
5. When only two zone operation is needed, any two of the three  
zone connections may be used. There is no inherent priority  
dependent on zone number.  
UNIT DAMAGE HAZARD  
SAFETY CONSIDERATIONS  
Improper installation, adjustment, alteration, service, maintenance,  
Failure to follow this caution may result in unit damage.  
TXV on indoor coil is required with all residential split  
system equipment.  
or use can cause fire, electrical shock, or other conditions which  
may cause personal injury or property damage. Consult a qualified  
installer, service agency or your distributor or branch for informa-  
tion or assistance. The qualified installer or agency must use  
factory-authorized kits or accessories when modifying this prod-  
uct. Refer to the individual instructions packaged with the kits or  
accessories when installing.  
INTRODUCTION  
The Carrier 3-Zone system allows the air conditioning and heating  
equipment to control temperatures in 3 distinct spaces or zones  
within a building. Each zone has independent temperature settings  
controlled by a conventional thermostat.  
Follow all safety codes and wear safety glasses. Have fire  
extinguisher available. Read these instructions thoroughly and  
follow all warnings or cautions attached to the unit. Consult local  
and state building codes and Sheet Metal and Air Conditioning  
National Association (SMACNA) for special installation require-  
ments.  
There are two distinct controllers:  
ZONECC3ZAC01 - Single Stage Heat / Single Stage Cool  
using conventional single stage thermostats.  
ZONECC3ZHP01 - Three Stage Heat / Two Stage Cool  
compatible for HP and multi-stage application thermostats and  
equipment.  
Recognize safety information. This is the safety-alert symbol  
.
Each system controller is comprised of a three-zone controller and  
a duct temperature sensor.  
When you see this symbol on the unit or in instructions and  
manuals, be alert to the potential for personal injury.  
NOTE: Thermostats are purchased separately.  
Understand the signal words DANGER, WARNING, and CAU-  
TION. These words are used with the safety-alert symbol. DAN-  
GER identifies the most serious hazards which will result in severe  
personal injury or death. WARNING signifies hazards which  
could result in personal injury or death. CAUTION is used to  
identify unsafe practices which would result in minor personal  
injury or product and property damage. NOTE is used to highlight  
suggestions which will result in enhanced installation, reliability,  
or operation.  
The comfort temperature settings can change automatically  
through the use of schedules if programmable thermostats are  
selected. This allows the Carrier 3-Zone to change the temperature  
settings in zones to reflect occupancy or usage. The Carrier 3-Zone  
system uses motorized air volume control dampers (also called  
zone dampers) to regulate the flow of conditioned air into the  
zones.  
INSTALLATION  
Step 1—Check Equipment and Job Site  
INSTALLATION CONSIDERATIONS  
Before the actual installation of a zoning system can begin,  
decisions need to be made to determine the number and location of  
zones. This affects duct and damper selections.  
INSPECT EQUIPMENT — File claim with shipping company,  
prior to installation, if shipment is damaged or incomplete.  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Book  
Tab 3a 5a 2a 5a  
1
1
4
4
PC 101  
Catalog No. 809-50009  
Printed in U.S.A.  
Form ZONEKIT-15SI  
Pg 1  
11-04  
Replaces: NEW  
 
need not be perfect because there will be positive pressure inside  
the cover. Do not mount the dampers with their actuators hanging  
directly beneath the ductwork. It is best to mount the actuator  
facing in either the three or nine o’clock position.  
11/2 " TO 2"  
INSULATION  
For specific duct types, follow instructions below:  
ROUND METAL DUCT WORK  
1. Crimp end of branch duct.  
2. Slip end of zone damper over end of duct work. Use  
self-tapping sheet metal screw to secure. (See Fig. 2.)  
3. Properly seal joint using duct tape, mastic, or other approved  
method. Do not allow mastic to come in contact with actuator.  
4. Insulate damper using 1-1/2 in. to 2-in. insulation. (Check  
your local codes.)  
A95131  
Fig. 3—Insulated Rectangular Metal Duct Work  
NOTE: All zone dampers and duct work must be properly  
supported according to local codes or SMACNA standards.  
ROUND FLEXIBLE DUCT WORK  
RECTANGULAR METAL DUCT WORK  
1. Slip 1 end of flexible duct work over 1 end of zone damper.  
(See Fig. 4.)  
1. Make connections using S-lock and drives. (See Fig. 2.)  
2. Properly seal joint using duct tape, mastic, or other approved  
method. Do not allow mastic to come in contact with actuator.  
ZONE  
DAMPER  
FLEXIBLE  
DUCT  
MOUNTING  
HUB  
ACTUATOR  
HOUSING  
A95132  
Fig 4—Round Flexible Duct Work  
OPN COM CLS  
2. Secure flexible duct to zone damper using SMACNA or other  
approved method.  
QUICK BLADE  
RELEASE  
BUTTON (RED)  
MOUNTING  
PLATE  
3. Properly seal joint using duct tape, mastic, or other approved  
method. Do not allow mastic to come in contact with actuator.  
4. Insulate damper using 1-1/2 in. to 2-in. insulation. (Check  
your local codes.) (See Fig. 5.)  
NOTE: All zone dampers and duct work must be properly  
supported according to local codes or SMACNA standards.  
FIELD  
INSTALLED  
POWER WIRING  
1/2STEEL STRAP  
C02083  
Fig. 1—Damper 24-vac Connections  
S-LOCK  
A95133  
Fig. 5—Insulated Round Duct Work  
SUPPLY  
AIR DUCT  
RECTANGULAR FIBROUS GLASS DUCT WORK  
DRIVE  
1. Insert 1 end of zone damper into 1 end of fibrous glass duct  
work approximately 2 to 3 in. (See Fig. 6.)  
ZONE  
DAMPER  
2. Screw field-supplied screws and tabs into zone damper.  
3. Properly seal joint using duct tape, mastic, or other approved  
method. Do not allow mastic to come in contact with actuator.  
A92478  
Fig. 2—Rectangular Metal Duct Work  
3. Insulate damper using 1-1/2 in. to 2-in. insulation. (Check  
your local codes.) (See Fig. 3.)  
4. Insulate damper using 1-1/2 in. to 2-in. insulation. (Check  
your local codes.) (See Fig. 7.)  
3
 
through the wall of the fan coil or may be located entirely inside  
the fan coil near the blower inlet. Anchor firmly in place with cable  
ties so that it cannot interfere with the blower wheel.  
FIBROUS  
GLASS  
DUCTWORK  
FIELD  
SUPPLIED  
SCREWS  
ZONE  
DAMPER  
SYSTEM WIRING  
Wiring the system is best done in four steps. Thermostats,  
Equipment, Dampers, and Remainder. The descriptions below and  
Table 1 will help you choose the correct wiring diagram for your  
system. Table 1 also shows the proper setting of dipswitches 9 and  
10 for each diagram. Based on the equipment, 3-zone control, and  
thermostat type, select the appropriate wiring diagram. Terminal  
designations on all the thermostats are those of Carrier thermostats.  
Other brands may vary somewhat. Wiring diagrams and 3-Zone  
Control board layouts are located at the end of this Installation  
Instruction.  
2TO 3″  
A92480  
Fig. 6—Rectangular Fibrous Glass Duct Work  
Table 1—Wiring Diagram Selection Chart  
3-ZONE  
TYPE  
STAT  
TYPE  
11/2TO 2″  
WIRING DIAGRAM EQUIPMENT  
SWITCH 9 SWITCH 10  
INSULATION  
1-spd. AC,  
Fig. 10  
AC  
AC  
AC  
HP  
not present not present  
1-Stg. heat  
1-spd. AC,  
Fig. 11  
A95134  
HP/2S  
HP/2S  
ON  
OFF  
OFF  
ON  
ON  
OFF  
ON  
1 or 2-stg. heat  
Fig. 7—Insulated Rectangular Fibrous Glass  
Duct Work  
1-spd. HP,  
Fig. 12  
1-stg. aux heat  
1-spd. HP,  
Fig. 13  
HP/2S AC (2 ht)  
HP/2S 2S (AC)  
HP/2S 2S (HP)  
Step 5—Install Barometric Bypass Damper  
1-stg. aux heat  
2-spd. AC,  
Fig. 14  
NOTE: The barometric bypass damper is a critical part of Carrier  
3-Zone System for controlling noise at minimum airflow. A  
barometric bypass should be installed unless the duct work and  
indoor unit have been sized for use without a bypass.  
ON  
1 or 2-stg. heat  
2-spd. HP,  
Fig. 15  
OFF  
OFF  
1-stg. aux heat  
Fig. 8 - Shows the board layout for the AC Control.  
The bypass should be installed according to local codes and  
SMACNA standards. Be sure bypass is properly supported.  
Fig. 9 - Shows the board layout for the HP/2S Control.  
Fig. 10 - Shows the 3-Zone AC Control wiring. It supports only 1  
stage cooling and 1 stage heating.  
Fig. 11 - Shows that the 3-Zone HP/2S Control may be used in 1  
stage cooling and 1 or 2 stage heating applications. For 2 stage  
heating, the stat may be a 2 stage heat AC stat or a HP stat  
converted to AC. (Carrier HP stats can be field converted to 2 stage  
heat AC stats.)  
Fig. 12 - Shows the conventional HP system, using a HP stat. Only  
single stage auxiliary heat is supported for heat pump systems.  
Using the HP stat allows control of emergency heat directly from  
the stat.  
Fig. 13 - Is also a HP system, but uses an AC stat with 2 stage  
heating instead of a HP stat. (Carrier HP stats can be field  
converted to 2 stage heat AC stats.) Here, emergency heat can only  
be selected by a switch on the 3-Zone Control.  
For proper installation, refer to Installation Instructions packaged  
with barometric bypass.  
Step 6—Install Leaving Air Temperature (LAT) Sensor  
NOTE: The supplied LAT sensor must be installed for normal  
operation. Heat pump systems may use an optional HPT (heat  
pump temperature) sensor for added protection. These sensors  
protect the equipment when leaving air temperatures approach  
excessive levels.  
Locate LAT sensor in main supply trunk after heating and cooling  
coil and before bypass damper and first branch. The LAT sensor is  
radiant shielded to prevent heat from affecting correct air tempera-  
ture.  
1. Drill a 1/4-in. hole at location in supply trunk where sensor  
will be installed.  
Fig. 14 - Is a 2 speed AC system and may have 1 or 2 stages of  
heat. An HP/2S Control and a 2S stat set for AC operation must be  
used.  
2. Insert sensor in hole and use as a template to mark the 2  
mounting holes.  
Fig. 15 - Is for a 2 speed HP. It requires an HP/2S Control and a  
2S stat set for HP operation. Only single stage auxiliary heat is  
supported for heat pump systems.  
3. Drill two 1/16-in. holes to accept No. 6 screws through  
pre-drilled holes in duct temperature sensor back plate.  
4. Use 2 No. 6 sheet metal screws to mount duct temperature  
sensor to unit.  
Step 1—Wire Thermostats  
All zone thermostats are wired identically, so only the Zone 1  
thermostat is shown on the wiring diagrams. For physical location  
of connections on 3-Zone Control refer to Fig. 8 (AC Control) or  
9 (HP Control).  
5. Connect sensor to 2-conductor wire using provided wire nuts.  
(See Fig. 9, 10, or 11 for connection to Carrier 3-Zone  
System.)  
Step 7—Install Heat Pump Temperature (HPT) Sensor  
Battery or power stealing thermostats may not require the C  
connection. Refer to thermostat Installation Instructions. Be care-  
ful not to cross zone numbers.  
The optional HPT sensor is recommended in all heat pump/fan coil  
installations. If an optional HPT sensor is not used, the 10K ohm  
resistor attached to the two HPT terminals on the board must be  
left in place. The HPT sensor measures the temperature of the air  
leaving the indoor coil. The sensor is to be installed downstream of  
the indoor coil but before the electric heaters. It can be installed  
Step 2—Wire Equipment  
Again, from the selected Fig. 10 through 13, make each connection  
as shown at the indoor and outdoor units and the 3-zone Control.  
4
 
Fuse  
To 24VAC  
Power  
Zone  
Zone  
Zone  
Rz  
C
R
Relay  
Relay  
Relay  
C
Rc/Rh  
Twist Of f  
To Zone  
Thermostat  
Y1  
W1  
G
Power Supply  
Rh  
Rc  
Y1  
W1  
ToEquipment  
G
R
C
To Zone  
Thermostat  
CLS_1  
COM_1  
OPN_1  
Y1  
W1  
G
To Zone 1  
Damper  
Damper 1  
Damper 2  
Triac  
Triac  
Triac  
Triac  
Triac  
Triac  
CLS_  
2
To Zone 2  
Damper  
COM_2  
OPN_ 2  
Micro  
CLS_ 3  
COM_3  
OPN_ 3  
To Zone 3  
Damper  
Damper 3  
R
C
To Zone  
Thermostat  
Y1  
W1  
G
Y1  
W
G
Status  
LAT  
LATC  
ToLAT  
Sensor  
ON  
1
2
3
4
5
6
7
Compressor  
Timer Override  
Dipswitches 1-8  
A04192  
Fig. 8—AC or 1-Stage System Wiring Diagram  
To 24VAC  
Power  
Zone  
Zone  
Zone  
R
C
R
Relay  
C
Rc/R  
Twist Off  
Y1  
W1  
G
Power Supply  
Relay  
To Zone 1  
Thermostat  
Rh  
Rc  
Y1  
Y2  
Relay  
Relay  
W2  
O
To  
W1  
Equipment  
G
Y2  
Fuse  
W2  
O
Relay  
R
C
CLS_1  
COM_1  
OPN_1  
Y1  
W1  
G
Relay  
To Zone 2  
Thermostat  
To Zone 1  
Damper  
Triac  
Y2  
CLS  
2
Damper 1  
W2  
O
To Zone 2  
Damper  
COM_2  
Triac  
OPN  
CLS  
2
Micro  
Triac  
Damper  
2
3
To Zone 3  
Damper  
Triac  
Triac  
Triac  
COM_3  
OPN  
R
3
Damper 3  
C
Y1  
W1  
G
To Zone 3  
Thermostat  
HP  
HPT  
To HPT  
Sensor  
E-Heat  
Y1  
W
G
Y2  
W
O
Status  
Y2  
W2  
O
LAT  
LATC  
To LAT  
Sensor  
ON  
1
ON  
2
3
4
5
6
7
1
2
3
E-Heat  
Compressor  
Timer Override  
Dipswitches 1 - 12  
A04191  
Fig. 9—HP or 2-Stage System Wiring Diagram  
Connect the equipment R to both Rz and either Rh or Rc. A jumper  
will be needed. Rc and Rh are internally connected but may be  
separated by breaking a twist-off (see step 4 below).  
Step 4—Wire Remainder  
Connect the LAT sensor to the LAT and LATC terminals. Polarity  
does not matter. If used, connect the HPT sensor to the HPT and  
HPTC terminals. If the HPT sensor is not used, you must leave the  
10K ohm resistor connected in its place.  
Step 3—Wire Dampers  
Each damper has three connections: Close, Open, and Common.  
Find the connection points along the lower left side of the 3-Zone  
Control. Suggested colors are Close = red; Open = green; Common  
= white. Field label and make the connections at the dampers and  
at the 3-Zone Control. Be careful not to cross zone numbers.  
If the cooling and heating systems have separate transformers,  
twist off the Rc/Rh jumper using a pair of long nosed pliers. Then  
connect the R of the cooling transformer to Rc, the R of the heating  
transformer to Rh and the common of both transformers to C.  
Connect a jumper wire between Rz and Rc. Rc powers G, Y, and  
O outputs. Rh powers W outputs.  
5
 
UNDERSTANDING SYSTEM OPERATION  
(READ BEFORE STARTING SYSTEM)  
Mode and Damper Positions  
Timer Override  
A momentary switch is located near the bottom of the control  
circuit board. Pressing it momentarily overrides all of the system  
timers, allowing the control to immediately jump to the highest  
calling stage.  
The thermostats determine the system heating or cooling mode.  
The first call in any zone sets the mode to satisfy that call. It will  
remain in that mode until all calls in that mode are satisfied and the  
equipment has been off for the time set by the auto changeover  
time dipswitches. (See Timers section.)  
Temperature Limits and Sensors  
Both the AC and HP controls have a LAT (leaving air temperature)  
sensor which is to be placed in the downstream air path of the  
heating /cooling equipment. It is used in both heating and cooling  
to limit LAT to a safe value. It must be connected. The system will  
not operate without it. Its setting is fixed for cooling and is  
adjustable in four settings for heating. Selection of best setting is  
discussed under LAT Limit Selection.  
In normal heating or cooling, the damper of any zone with a call  
in the current mode will be open and all other zones will be closed.  
When there is no call, any zone with its fan set to ON will be open,  
and any zone with its fan set to AUTO will be closed. If any zone  
fan is set to ON, the blower will be energized.  
If all fan settings are AUTO, the dampers will remain in their last  
position before the equipment turned off and the blower will be  
off. (This normally means one damper open and all others closed.)  
The HP control also has an optional HPT Sensor (heat pump  
temperature) which is to be placed downstream of the coil but  
ahead of the electric heater. This sensor measures the temperature  
of the air leaving the coil during HP heating. It is not included with  
the control, but may be ordered separately as part number  
TSATXXSEN01-B. A 10K ohm resistor is factory installed in its  
place when the actual sensor is not used. In the HP control only,  
dipswitch 11 allows the installer to temporarily disable both the  
LAT and the HPT sensors. Disabling of these sensors is only to be  
done on a temporary basis.  
When dampers are to move, all opening is done first, followed by  
all closing.  
Stages  
In multi-stage systems, the equipment stage is set by the greatest  
thermostat call, but may be delayed by the control’s cycle and  
staging timers. (See timers explanation below.) The AC Control  
supports only single stage heat and cool. The HP control supports  
two stage cooling, two stage furnace heating, and three stage HP  
heating (lo HP, hi HP, hi HP + aux heat.)  
UNIT DAMAGE HAZARD  
Emergency Heat  
Failure to follow this caution may result in unit damage.  
Operating equipment with sensors disabled can cause perma-  
nent damage to HVAC equipment.  
Emergency heat (aux heat without compressor heat) can be  
selected for a HP system by either of two ways: First, by selecting  
Eheat using the Eheat override switch on the HP Control, or  
second, selection of Eheat on each of the thermostats, provided  
they have the Eheat function. When either of these Eheat selections  
is made, a heating demand provides a W signal without a Y signal  
to the equipment.  
Bypass  
The purpose of a bypass is to limit noise in the duct system when  
the dampers are excessively restricting it. When a direct bypass  
(outlet air fed back directly into the return) is used, bypassing  
decreases entering air temperature in cooling and increases it in  
heating. Excessive bypassing will lead to limit trips, either through  
the LAT /HPT sensors or the equipment internal limits.  
NOTE: The second Eheat method requires HP thermostats and  
that they all must be set to Eheat.  
Indicator LEDs  
There are 7 indicator LEDs on the AC Control and an additional 3  
on the HP/2S Control. Their locations are shown on Fig. 8 and 9.  
Setting the Bypass  
Setting the bypass is a balance between too much noise (bypass  
trip pressure set too high) and excessive bypassing which will  
cause limit trips, diminishing performance. As a general rule, the  
bypass should remain closed as much as possible. It should never  
open when all the dampers are open and only open as much as  
needed to bring noise to an acceptable level when only one damper  
is open. (See System Setup for details.)  
Each damper has its own green LED which is ON when the  
damper opens due to a calling condition or partially open due to an  
LAT or HPT limit condition.  
Each equipment output has its own LED which is on when that  
output is energized. Y and O outputs are yellow, W outputs are red  
and the G output is green.  
In addition, there is a status LED whose operation is described  
LAT Limit Selection  
under the section Error Codes.  
Cycling on internal equipment limits is to be avoided because it  
overstresses and can shorten the life of the equipment. Therefore,  
the LAT limit setting should be selected to trip below the  
equipment limit. See System Setup for details on how to choose  
one of four available LAT limits.  
Timers  
To control excessive equipment cycling or rapid staging up, the  
control has two timers. The cycle timer prevents the same stage  
from turning on within 10 minutes of the last time it turned on.  
This allows a stage to turn on for as short or as long as the  
thermostats request, but will not allow more than six cycles per  
hour.  
Limit Levels and Actions  
The response of the system to the LAT/HPT sensors are shown in  
Table 2. Cooling and HP limits are not adjustable. Looking at  
Table 2, there are eight limit level index numbers, 0 through 7.  
These represent the closeness of the actual LAT/HPT temperatures  
to the final shutdown limit. 0 represents no limit challenge while  
7 indicates a final shutdown of the equipment. Note that progres-  
sive actions are taken by the control as the LAT/HPT limit is  
approached. Each action progressively reduces the limit challenge  
by increasing airflow. Normally, the system will stabilize at limit  
level 1 or 2 because opening all closed dampers 2 or 4 positions  
(out of 15) will reduce LAT to a level below its limit.  
The staging timer prevents a higher stage from turning on until the  
next stage below it has been on for 15 minutes. This minimizes use  
of electric heat with heat HP systems.  
There is also a timegaurd timer which will not allow the compres-  
sor to be turned on until it has been off for five minutes.  
A changeover timer, which can be set from 0 to 30 minutes, limits  
the control’s ability to switch between heating and cooling. The  
opposite mode is prevented from coming on until the first mode  
has been satisfied for the selected time.  
6
 
Table 2—Limit Temperature Levels and Actions  
LIMIT LEVEL  
0
1
2
3
4
5
6
7
Cooling Limit (40 deg) above  
HP limit (115 deg) below  
Heat Limit (130 deg) below  
Heat Limit (145 deg) below  
Heat Limit (160 deg) below  
Heat Limit (175 deg) below  
LIMIT ACTIONS  
47  
46  
45  
44  
43  
42  
41  
40  
107  
119  
131  
143  
155  
108  
121  
133  
145  
158  
109  
122  
135  
148  
161  
110  
124  
137  
150  
164  
111  
125  
139  
153  
166  
112  
127  
141  
155  
169  
113  
128  
143  
158  
172  
115  
130  
145  
160  
175  
ClosedDamper Positions  
Allowed stages (1 stg)  
Allowed Stages (2 stg)  
Allowed stages (3 stg)  
0
1
2
3
2
1
2
3
4
1
2
3
6
1
1
2
8
1
1
2
10  
1
12  
1
14  
0
1
1
0
1
1
0
Using Limit Level Indicator  
There are 8 dipswitch settings on the AC zone control and an  
additional 4 on the HP board. Below is a table summarizing their  
function. Below the table is a more detailed description of what  
each does and how to set it properly for your application.  
The final setting of the bypass for best performance has always  
been something of a black art. The 3-Zone System has a new  
feature to simplify this adjustment. While the system is operating,  
these limit level numbers, if greater than zero, are flashed on the  
status LED.  
Table 3—Dipswitch Settings  
ACTION  
(OFF)  
ACTION  
(ON)  
DIPSWITCH 1 POSITION  
Once the proper LAT limit choice is made based on equipment  
maximum rise, the limit level indicator assists in setting the bypass  
pressure adjustment. See System Setup for details.  
Defeat  
Auto Changeover  
Timer  
Auto changeover Timer  
Active  
1
Installer Test Mode  
Auto Changeover 20 Min-  
utes  
Auto Changeover  
30 Minutes  
2
3
Dipswitch 4 selects a special Installer Test Mode, designed to  
assist the installer (or service person) to commission the system. It  
verifies damper movement in proper zone and that the heating and  
cooling equipment operates properly at each stage. When this  
mode is selected, by moving dipswitch 4 to ON, the following  
sequence will be executed once:  
Auto Changeover Timer X  
1
Auto Changeover  
Timer X .5  
4
5
6
7
8
Normal Operation  
Zoning Enabled  
Fan With W Disabled  
LAT Setting  
Installer Test  
Zoning Disabled  
Fan With W Enabled  
LAT Setting  
Step 1 — Two minutes, one flash of status LED. The blower is  
LAT Setting  
LAT Setting  
energized with G, damper 1 opens, and other dampers are closed.  
Table 4—Dipswitch Settings  
for HP Control Only  
Step 2 — Two minutes, two flashes of LED: With the blower on,  
damper 1 closes and damper 2 opens.  
Step 3 — Two minutes, three flashes of LED: With the blower  
ON, damper 3 opens and damper 2 closes.  
ACTION  
(OFF)  
ACTION  
(ON)  
DIPSWITCH 2 POSITION  
9
HP Operation  
HP Thermostat  
AC Operation  
Step 4 — Two minutes, four flashes of LED: All dampers open,  
first stage of heat turns on. For HP control only, this is followed by  
the second stage of heat (HP plus aux heat, hi HP, or hi furnace)  
for two more minutes. For HP control with two stage compressor,  
the third stage of heat (hi HP plus aux heat) comes on for a third  
2 minute period.  
10  
AC Thermostat  
LAT and HPT  
Safeties Enabled  
LAT and HPT  
Safeties Disabled  
11  
12  
Reversing Valve Ener-  
gized in Cooling (O) Energized in Heating (B)  
Reversing Valve  
Step 5 — Two minutes, five flashes of LED: All dampers are open  
and first stage of cooling turns on for 2 minutes. For HP board  
only, second stage of cooling comes on for an additional 2  
minutes.  
Dipswitches  
Dipswitch 1- This determines whether or not a minimum time  
must pass before the control is allowed to transition between  
heating and cooling or vice versa. If it is set to ON, there is no time  
requirement. Default is OFF.  
Dipswitch 2 - This switch, together with dipswitch 3, determines  
the changeover time, effective if switch 1 is OFF. ON sets 30  
minutes. OFF sets 20 minutes. Default is OFF.  
Dipswitch 3 - This is a multiplier, modifying the time set on switch  
2. ON multiplies the set time by 0.5. OFF multiplies the set time  
by 1.0. Default is OFF.  
At the end of Step 5, the control returns to normal operation. To  
restart the test sequence, the switch must be moved to OFF and  
then back to ON.  
If zoning is disabled (Switch 5 = ON), the procedure above will be  
followed, except all the dampers will remain open throughout the  
sequence.  
Dipswitch 4 - This selects the Installer Test Mode, used to check  
system operation. Details are provided in section Installer Test.  
ON selects Installer Test. OFF selects normal operation. Default is  
OFF.  
Dipswitch 5 - Enables and disables zoning. ON disables zoning,  
with all dampers open and zone 1 thermostat controlling. OFF  
selects normal zoning operation. Default is OFF.  
SYSTEM SETUP  
Thermostats  
Read the thermostat Installation Instructions and be sure to  
complete the required setup of these devices before using them to  
bring on the equipment. If the thermostats have a zoning″  
selection, be sure to turn it on. This will eliminate the timers within  
the thermostat and allow the 3-Zone control’s timers to do their  
job.  
Dipswitch 6 - Selects G ON or OFF with W. Selecting ON causes  
G to be energized whenever W is energized. Selecting OFF does  
7
 
not bring on G with W. Default is OFF.  
Automatic Checkout  
Dipswitch 7 and 8 - Sets LAT limit temperature. See LAT Limit  
Selection for proper setting. Default is OFF = 145° limit.  
The following dipswitches are on the HP/2S control only:  
Dipswitch 9 - Informs the control whether it is connected to a heat  
pump or an air conditioner. OFF selects HP. ON selects AC.  
Default is OFF (HP).  
Dipswitch 10 - Informs the control of the type of thermostat being  
used. OFF selects HP thermostat. ON selects AC thermostat. A HP  
thermostat may not be selected if the system selection is AC. A  
2-stage heat AC thermostat or a HP thermostat may be used with  
a single stage HP. Default is OFF.  
An automatic checkout procedure is provided which will exercise  
dampers, heating, and cooling in that order. It is described under  
the Understanding System Operation section in Installer Test  
Mode. This may be used or the system may be checked out  
manually by creating thermostat calls. When using thermostats,  
remember that only the calling zoning dampers will be open. This  
provides the means to select which dampers are open for any  
heating or cooling call. It is advisable that the initial checkout be  
made with all dampers open before the bypass is set. This can be  
done by temporarily setting Switch 5 to ON (disable zoning) and  
controlling the equipment from the Zone 1 thermostat. When the  
equipment is operating satisfactorily, return Switch 5 to OFF and  
proceed to the next section.  
Dipswitch 11 - Disables LAT and HPT safeties when ON. ON is  
intended only for emergencies. When ON is selected, there is no  
over/under temperature protection for the equipment. Default is  
OFF.  
Bypass Adjustment  
The bypass should be set to the highest possible pressure setting  
consistent with an acceptable air noise level. To set, operate the  
system with a call from the smallest zone at its highest airflow  
(highest may be either heating or cooling). This condition forces  
the largest amount of air through the smallest duct, creating the  
highest static pressure at the bypass. Adjust the bypass pressure  
setting so that the bypass stays closed. Then check to determine if  
the level of noise and blowin that zone is acceptable. If it is  
unacceptable, reduce the bypass pressure setting (see bypass  
instructions for how to adjust) until it just begins to crack open.  
Check again, continuing the process until an acceptable noise and  
blowlevel is reached.  
If, under this condition, the LAT approaches its limit, the system  
will open the other closed dampers until the LAT reaches an  
acceptable level. This operation is acceptable. The system will  
automatically open dampers enough to keep the LAT at a safe  
value, and will do it only when the zone demands require it. You  
may observe the limit level on the status LED (if it is above zero).  
If it stabilizes at a value of higher than 2, an overly small duct  
system is indicated and it would be desirable to raise the bypass  
pressure setting, if possible.  
Dipswitch 12 - Informs the control whether the reversing valve is  
energized in cooling (O function) or heating (B function). ON  
selects B function. OFF selects O function. Default is OFF.  
LAT Limit Selection  
To accommodate varying heat rises in furnaces and fan coils, the  
LAT limit adjustment has four selections: 130, 145, 160 and 175  
degrees. In addition to these, the HPT limit is fixed at 115 degrees  
and the cooling limit (also sensed by LAT sensor) is 40 degrees.  
To select the proper limit, check or calculate the rated maximum  
rise of the equipment. Add 75 degrees to this value. Pick the  
closest LAT limit choice below this value and use dipswitches 7  
and 8 to enter this value using:  
Table 5—LAT Limit  
TEMPERATURE  
SWITCH 7  
OFF  
SWITCH 8  
ON  
130  
145 (default)  
160  
OFF  
OFF  
ON  
OFF  
175  
ON  
ON  
Error Codes  
The status LED indicates normal operation, problems, and  
LAT/HPT limit status according to a two digit code. The first digit  
flashes its number, followed by a 2 second pause, followed by the  
second digit, followed by a 4 second pause. The cycle the repeats.  
The codes are:  
Take a minute to study the LAT Limit table. Note that the limits  
are the final shutdown temperatures, but actions begin earlier.  
First, at levels 1 and 2, closed dampers begin to open gradually,  
followed at level 3 by staging down of multi stage equipment, if it  
exists. Under most limit challenges, the system will stabilize  
between 1 and 3 due to opening of closed dampers.  
Table 6—Error Codes  
ON CONTINUOUSLY  
NO PROBLEMS  
LAT limit level 1 - 7  
HPT limit level 1 - 7  
LAT shorted  
11 - 17  
21 - 27  
31  
UNIT DAMAGE HAZARD  
Failure to follow this caution may result in unit damage.  
Setting LAT limit too high can shorten the life of the HVAC  
equipment.  
32  
LAT open  
33  
HPT open  
34  
HPT shorted  
41  
Invalid: Sw 9=ON; Sw 10=OFF  
8
 
POWER  
Rz  
C
FURNACE  
OR  
FAN COIL  
ZONE 1  
AC TSTAT  
ZONE 1  
INPUT  
EQIUPMENT  
AIR  
R
C
R
C
R
C
CONDITIONER  
Rh  
Rc  
Y1  
C
Y
Y/Y2  
Y1  
W1  
G
Y
W
G
COOL  
HEAT  
FAN  
W1  
G
G
AC 3-ZONE CONTROL  
Fig. 10 — AC 3-Zone Control, AC STAT, 1-Stg. AC  
with 1-Stg. Heat  
A04196  
POWER  
Rz  
C
FURNACE  
AIR  
ZONE 1  
INPUT  
OR  
ZONE 1  
AC TSTAT  
CONDITIONER  
EQIUPMENT  
FAN COIL  
R
C
R
C
R
C
R
C
Y
C
Y
COOL  
Y/Y2  
Y1  
W1  
G
Y1  
(LO) HEAT  
FAN  
W1  
G
G
G
Y2  
Y2  
SWITCH 9=ON  
SWITCH 10=ON  
W2  
O
W2  
O
W2  
(HI HEAT)  
HP/2S 3-ZONE CONTROL  
Fig. 11 — HP/2S 3-Zone Control, AC Stat, 1-Stg. AC  
with 1 or 2-Stg. Heat  
A04197  
POWER  
Rz  
C
ZONE 1  
INPUT  
ZONE 1  
EQIUPMENT  
AC TSTAT  
FAN COIL  
HEAT PUMP  
Rh  
Rc  
R
C
R
C
R
C
Y
R
C
Y
HT AND CL  
AUX HT  
FAN  
Y/Y2  
Y1  
W1  
G
Y1  
W1  
G
W
G
G
Y2  
Y2  
SWITCH 9=OFF  
SWITCH 10=OFF  
W2  
O
W2  
O
REV VALVE  
O
O
H P/2S 3-ZONE CONTROL  
Fig. 12 — HP/2S 3-Zone Control, HP Stat, 1-Stg. HP  
with 1-Stg. Aux. Heat  
A04198  
9
 
POWER  
Rz  
C
ZONE 1  
INPUT  
ZONE 1  
EQIUPMENT  
AC TSTAT  
FAN COIL  
HEAT PUMP  
Rh  
Rc  
R
C
R
C
R
C
Y
R
C
Y
COOL  
HP HEAT  
FAN  
Y/Y2  
Y1  
W1  
G
Y1  
W1  
G
W
G
W2  
G
Y2  
Y2  
SWITCH 9=OFF  
SWITCH 10=ON  
W2  
O
W2  
O
AUX HEAT  
O
O
H P/2S 3-ZONE CONTROL  
Fig. 13 — HP/2S 3-Zone Control, AC Stat, 1-Stg. HP  
with 1-Stg. Aux. Heat  
A04199  
POWER  
Rz  
C
2 SPEED  
AIR  
CONDITIONER  
FURNACE  
OR FAN  
COIL  
ZONE 1  
INPUT  
ZONE 1  
2SACTSTAT  
EQIUPMENT  
Rh  
Rc  
R
C
R
C
R
C
R
C
LO COOL  
Y1  
Y1  
Y1  
Y1  
(LO) HEAT  
FAN  
W1  
G
W1  
G
G
G
Y2  
Y2  
Y2  
Y2  
HI COOL  
Y/Y2  
SWITCH 9=ON  
SWITCH 10=ON  
W2  
O
W2  
O
W2  
(HI HEAT)  
HP/2S 3-ZONE CONTROL  
Fig. 14 — HP/2S 3-Zone Control, AC Stat, 2-Spd AC  
with 1 or 2-Stg. Heat  
A04200  
POWER  
Rz  
C
ZONE 1  
ZONE 1  
EQIUPMENT  
INPUT  
HEAT PUMP  
2S AC TSTAT  
FAN COIL  
Rh  
Rc  
R
C
R
C
R
C
R
C
LO HT AND CL  
AUX HT  
Y1  
Y1  
Y1  
Y1  
W1  
G
W1  
G
W
G
W2  
FAN  
G
Y2  
Y2  
Y2  
O
Y2  
O
HI HT AND CL  
REV VALVE  
Y/Y2  
SWITCH 9=ON  
SWITCH 10=ON  
W2  
O
W2  
O
H P/2S 3-ZONE CONTROL  
Fig. 15 — HP/2S 3-Zone Control, HP Stat, 2-Spd HP  
with 1-Stg. Aux. Heat  
A04201  
10  
 
11  
 
SERVICE TRAINING  
Packaged Service Training programs are an excellent way to increase your  
knowledge of the equipment discussed in this manual, including:  
• Unit Familiarization • Maintenance  
• Installation Overview • Operating Sequence  
A large selection of product, theory, and skills programs is available, using popular  
video-based formats and materials. All include video and/or slides, plus companion  
book.  
Classroom Service Training plus "hands-on" the products in our labs can mean  
increased confidence that really pays dividends in faster troubleshooting, fewer  
callbacks. Course descriptions and schedules are in our catalog.  
CALL FOR FREE CATALOG 1-800-644-5544  
[ ] Packaged Service Training [ ] Classroom Service Training  
A94328  
Copyright 2004 CARRIER Corp. • 7310 W. Morris St. • Indianapolis, IN 46231  
zkit15si  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Book  
Tab 3a 5a 2a 5a  
1
1
4
4
PC 101  
Catalog No. 809-50009  
Printed in U.S.A.  
Form ZONEKIT-15SI  
Pg 12  
11-04  
Replaces: NEW  
 

Blackberry Water System 600 User Manual
Black Decker Iron AS390 User Manual
Blodgett Fryer B16 PF45 User Manual
Blue Rhino Charcoal Grill CBT672B User Manual
BRK electronic Fire Extinguisher FE3A40GR 6 User Manual
Bushnell Binoculars 161001CM User Manual
Cables Unlimited Headphones SPK 24G User Manual
Campbell Hausfeld Air Compressor IN228704AV User Manual
Candy Washer ICW101TRC User Manual
Chief Manufacturing Indoor Furnishings PLP Series User Manual